HIGH AND LOW PRESSURE SWITCH TEST - Continued
CHAPTER 8 - SECTION 9035 - ARCTIC/COLD WEATHER HEATER

Maintenance Manual For Hydraulic Excavator Model 230Lcr
Page Navigation
  627    628    629    630    631  632  633    634    635    636    637  
img
TM 5-3805-280-24-1
Tests
REFRIGERANT HOSES AND TUBING INSPECTION
hose and tube connections. Dip O-rings in correct
When a component is disconnected from the system,
viscosity oil before assembling.
special care should be given to inspecting hoses and
tubing for moisture, grease, dirt, rust, or other foreign
IMPORTANT: Hose used for air conditioning
material. If such contamination is present in hoses,
systems contains special barriers in
tubing, or fittings and cannot be removed by cleaning,
its walls to prevent migration of
then replace parts.
refrigerant gas.
Fittings that have grease or dirt on them should be
DO NOT use hydraulic hoses as
wiped clean with a cloth dampened with alcohol.
replacement hoses in the air
Chlorinated solvents (such as trichloroethylene) are
conditioning system. Use ONLY
contaminants, and must not be used for cleaning.
certified hose meeting SAE J51B
requirements.
To assist in making leak-proof joints, use a small
amount of clean correct viscosity refrigerant oil on all
TX,9031,UU3169 1913AUG961/1