• Home
  • Download PDF
  • Order CD-ROM
  • Order in Print
TRAVEL ALARM CIRCUIT DIAGNOSTIC PROCEDURES - Continued
OVERLOAD ALARM CIRCUIT SCHEMATIC

Technical Manual For Hydraulic Excavator Model 330Lcr 1
Page Navigation
  296    297    298    299    300  301  302    303    304    305    306  
img
.
TM 5-3805-281-24-1
Sub-System Diagnostics
OVERLOAD ALARM CIRCUIT OPERATIONAL
INFORMATION
The following conditions must be met for the circuit to
function:
Key switch ON
Voltage present at auxiliary power 10-amp fuse F19
CED,OUOE012,136
1916MAR991/1
OVERLOAD ALARM CIRCUIT THEORY OF
OPERATION
9015
15
100
The overload alarm circuit contains: proximity switch B32,
pressure switch B33, relay K16, and alarm H9.
Operating voltage for the overload alarm circuit is applied
from fuse F19, through terminal strip X27, terminal 1 to
the overload alarm power terminal, terminal 30 of relay
K16, and terminal 1 of the proximity switch. When the
boom is positioned on either side of the machine,
proximity switch B32 closes and energizes relay K16 by
applying +24 volts to relay terminal 85. With relay K16
energized, +24 volts is applied from terminal 87 to
pressure switch B33, enabling the pressure switch. If the
boom cylinder hydraulic pressure exceeds 3300 psi,
switch B33 closes, activating the alarm, by applying
ground to the overload alarm ground terminal.
CED,OUOE012,138
1916MAR991/1
4-168


Privacy Statement
Press Release
Contact

© Copyright Integrated Publishing, Inc.. All Rights Reserved.